In a building there are 15 bulbs of 45 W, 15 bulbs of 100 W, 15 small fans of 10 W and 2 heaters of 1 kW. The voltage of electric main supply is 220 V. The minimum fuse capacity (rated value) of the building will be:
We begin by noting that the electric fuse has to carry the total current drawn by all the appliances that may be switched on together. The current is obtained from power with the well-known relation:
where is the electric power in watts (W), is the supply voltage in volts (V) and is the current in amperes (A). Rearranging the formula, we obtain
To use this expression, we first calculate the total power consumption of the building by adding the power ratings of every device present.
We have 15 bulbs rated at 45 W each. So their combined power is
Now, 15 bulbs are rated at 100 W each. Hence
Next, 15 small fans are rated at 10 W each, giving
Finally, there are 2 heaters, each of 1 kW. Remembering that , we write
Adding all these powers gives the total power demand:
The supply voltage of the mains is given as 220 V. Substituting and in the rearranged power formula, we get the total current:
Numerically, this equals approximately . A fuse is chosen so that its rating is just above the maximum expected current; if it were below, the fuse would blow during normal operation. The next available standard rating higher than is .
Hence, the correct answer is Option D.